Loading... Please wait...

Add to Wish List

Click the button below to add the MNSPD-600 Midnite Solar Lightning Arrestor-600Vdc Surge Protector to your wish list.

You Recently Viewed...

Our Newsletter


MNSPD-600 Midnite Solar Lightning Arrestor-600Vdc Surge Protector

Price:
$209.00
SKU:
MN-LA-600
Weight:
1.00 LBS
Availability:
Chemainus BC, Victoria BC, Barrie ON
Shipping:
Calculated at checkout


Product Description

Midnite Solar 600V Surge Protection Device

Manufacturer Part Number: MNSPD-600

The MidNite SPD is a welcome replacement for less sophisticated arrestors that have been the mainstay of the industry for many years.

It is a 600V Surge Protector Device (MNSPD) is a Type 1 device designed for indoor and outdoor applications. Engineered for both AC and DC electric systems, it provides protection to service panels, load centers or where the SPD is directly connected to the electronic device requiring protection. Protection for gridtie PV combiners and inverter input circuits.

Specifications

Part No. MNSPD115 MNSPD300MNSPD600
Nominal Voltage 0 to 150 VDC 0 to 300 VAC 0 to 385 VDC 0 to 485 VAC 0 to 640 VDC
MCOV VRMS @1mA 180V (162-198) 470V (423-517) 780V (702-858)
ClampV @ 100A Current 8/20µs 295V 775V 1290V
I peak (8/20µs) (Current) 115kA (Full Device)
57.5kA (Each Section)
115kA (Full Device)
57.5kA (Each Section)
115kA (Full Device)
57.5kA (Each Section)
Energy Absorption 1120 J (Full Device)
560 J (Each Section)
3130 J (Full Device)
1560 J (Each Section)
4320 J (Full Device)
2160 J (Each Section)
Suggested Placement 12V,24V,48V DC battery circuits 120/240VAC circuits, offgrid PV combiners and charge controller inputs up to 300VDC 316V/480VAC circuits Grid tie PV combiners Grid tie inverter input
Diagnostics Dual Operating LED Indicators. When voltage is present Operating Temperature Range -40°c to +85°c
Nominal Discharge Current INA 57.5kA
Thermal Disconnector Internal
Response time <1micro sec

Detailed Description

The SPD is offered in three different voltages to maximize the required protection level. Protection is achieved by reducing the clamping voltage to a safe level that your system can sustain without damaging any electronics in the system. The MNSPD is designed to clamp a 115,000 amp surge! Blue LED’s provide visual indication of operation from a distance.

The MidNite Solar 600V Surge Protector Device (MNSPD) is a Type 1 device per UL1449 rev3. Protection for grid-tie PV combiners and inverter input circuits. Listed by ETL for US & Canada.

SPD Installation Video
SPD Comparison Test Video
SPD Install - Hawaii Video

Listed by ETL for US & Canada

Size: 4.4"L x 3.8"W x 3.5"D
Ind box: 5"L x 4"W x 4"D

Ind 1 Lbs


Find Similar Products by Category